1.6.2

Standard Controller

Power supply
Rated voltage
g
Operating voltage range
Frequency range
2)
External current I
Ext
Power consumption
Standard controller without options
without I
Ext
active power/apparent power
(capacitive)
Standard controller with options
without I
Ext
active power/apparent power
(capacitive)
Standard controller with options with
I
Ext
active power/apparent power
(capacitive)
Permissible voltage interruptions
Standard controller without options
without I
Ext
Standard controller with options
without I
Ext
Standard controller with options
with I
Ext
1)
including harmonic
2)
current transmitted from L+, BA, AA to external load
3)
The load voltage of the AA is reduced hereby to 13 V, L+ to 15 V and the BA to 14 V
Table 1-21
Power supply standard controller
SIPART DR22 6DR2210
C79000-G7476-C154-03
230 V AC
switchable
187 to 276 V
AC
8 W/17 VA
13 W/25 VA
26 W/45 VA
3)
≤ 90 ms
≤ 80 ms
≤ 50 ms
1 Technical Description
1.6.2 Standard Controller
115 V AC
93 to 138 V
20 to 28 V AC
AC
48 to 63 Hz
450 mA.
8 W/13 VA
8 W/11 VA
13 W/20 VA
13 W/18 VA
26 W/36 VA
28 W/35 VA
≤ 70 ms
≤ 55 ms
≤ 60 ms
≤ 50 ms
≤ 35 ms
≤ 35 ms
1.6 Technical Data
24 V UC
20 to 35 V
1)
DC
-- -- --
8 W
13 W
28 W
≤ 30 ms
≤ 25 ms
≤ 20 ms