3 Operation
3.3 Configuring level (parameterization and structuring mode)
3.3.2 Parameterization mode onPA (online parameters)
Digital display
y
x
w
Adjustment/
Adjustment/
display area
tFI
oFF, 1 to 1000
vvI
0.100 to 10,00
cPI
0.100 to 100.0
tnI
1,000 to 9984
tvI
oFF, 1.000 to 2,992
AHI
0.0 to 10.0
Y0I
Auto, 0.0 to 100.0
1)
YAI
--10.0 to 110.0
1)
YEI
--10.0 to 110.0
tFII
oFF, 1 to 1,000
vvII
0.100 to 10.00
cPII
0.100 to 100.0
tnII
1.000 to 9984
tvII
oFF, 1.,000 to 2,992
AHII
0.0 to 10.0
Y0II
Auto, 0.0 to 100.0
1)
YAII
--10.0 to 110.0
1)
YEII
--10.0 to 110.0
dr
0.080 to 8.000
tY
oFF, 1 to 1000
tA
20 to 600
tE
20 to 600
tYII
oFF, 1 to 1,000
tAII
20 to 600
tEII
20 to 600
tF1
oFF, 0.1 to 1000
tFb
oFF, 0.1 to 1000
c1
-1.999 to 19.999
c2
-1.999 to 19.999
c3
-1.999 to 19.999
c4
-1.999 to 19.999
c5
-1.999 to 19.999
c6
-19.99 to 19.99
c7
-19.99 to 19.99
c8
-1.999 to 19.999
c9
-1.999 to 19.999
P01
-1.999 to 19.999
P15
-1.999 to 19.999
1)
YE >YA
Table 3-1
Parameter list onPA
174
Factory
Resolution
setting
setting
1
128 values/octave
5.000
0.100
9984
oFF
128 values/octave
0.0
0.1
Auto
0.1
- -5.0
0.1
105.0
0.1
1
128 values/octave
5.000
0.100
9984
128 values/octave
oFF
0.0
0.1
0.1
Auto
--5
0.1
105,0,0
0.1
2)
0,80
0.080
oFF
128 values/octave
200
20
200
20
oFF
128 values/octave
200
20
200
20
1
128 values/octave
1
128 values/octave
0
0.001
0
0.001
0
0.001
1
0.001
0
0.001
0
0.01
0
0.01
0
0.001
0
0.001
1
0.001
0.001
1
Di-
Parameter meaning
men-
men-
sion
s
Filter time constant xdI
1
Derivative action gain
Proportional action factor
1
Integral action time
s
Derivative action time
s
%
Response threshold xdI
Operating point
%
Manipulated variable limiting start
%
Manipulated variable limiting end
%
s
Filter time constant xdII
1
Derivative action gain
Proportional action factor
1
Integral action time
s
Derivative action time Parameter set II
s
Response threshold xdII
%
Operating point
%
Manipulated variable limiting start
%
Manipulated variable limiting end
%
s
Display refresh rate
s
Floating time
ms
min. actuating pulse pause
min. actuating pulse length
ms
s
Floating time
min. actuating pulse
ms
pause
min. actuating pulse length
ms
s
Filter time constant AE1
s
Filter time constant AEb
Multiplicative constant
1
Multiplicative constant
1
Additive constant
100 %
Multiplicative constant
1
Additive constant
100 %
Multiplicative constant
1
Multiplicative constant
1
Additive constant
100 %
Multiplicative constant
1
1
connectable parameters
connectable parameters
1
2)
typical cycle times
Manual
Parameter set I
P-controller
P-controller
Controller II
when S1 = 12
only when S4 = 1
SIPART DR22 6DR2210
C79000-G7476-C154-03

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6dr2210

Table of Contents