Structure
Switch
Function
switches
position
S0
Identification of the user program
memorys
1)
[ 0 ]
Identification for factory setting (APSt)
1
ID number for various user programs
254
S1
Controller type
[ 0 ]
Fixed setpoint controller 2 independent
1
Fixed setpoint controller 2 dependent
2
DDC fixed setpoint controller
3
Follow-up/Synchronized/SPC controller
with Int/Ext switching
4
ratio controller
5
cascade control
6
ratio-cascade control
7
override control max. selection y
8
override control min. selection y
9
Process display
10
Fixed setpoint controller with 1 setpoint
(control system coupling)
11
Follow-up controller without Int/Ext
switching (control system coupling)
12
Double fixed setpoint/follow-up
controller
S2
Output structure
[ 0 ]
K-output
1
S-output internal feedback
2
S-output external feedback
S3
Mains frequency suppression
[ 0 ]
50 Hz
1
60 Hz
S4
Connection of input range
[ 0 ]
fixed connection
1
free connection
S5
Input signal AE1
[ 0 ]
0 . . . 20 mA without
1
0 . . . 20 mA with
2
4 . . . 20 mA without
3
4 . . . 20 mA with
S6
Input signal AE2
[ 0 ]
0 . . . 20 mA without
1
0 . . . 20 mA with
2
4 . . . 20 mA without
3
4 . . . 20 mA with
[
]
factory setting
1)
Position 0 cannot be set manually.
As soon as the factory setting is changed (parameters or structures) S0 is automatically set from 0 to 1, APSt sets S0 to 0, FPSt has no
influence.
Table 3-8
Structure switch tables
SIPART DR22 6DR2210
C79000-G7476-C154-03
3.3
Configuring level (parameterization and structuring mode)
setpoints
setpoints
}
transmitter
monitoring
MUF
}
transmitter
monitoring
MUF
3.3.6
Structuring mode StrS (structure switches)