Load dependence
Zero error
End value error
Linearity
Temperature influence
Zero point
Full scale
Static destruction limit
Measuring transducer feed L+
Rated voltage
Load current
Short-circuit current
Static destruction limit
Digital inputs BE1 to BE4
Signal status 0
Signal status 1
Input resistance
Static destruction limit
Binary outputs BA1 to BA8 (with wired or diodes)
Signal status 0
Signal status 1
Load current
Short-circuit current
Static destruction limit
Cycle time
A/D-conversion
Procedure
Modulation range
Resolution
Zero error
Full scale error
Linearization error
Temperature influence
Zero point
Full scale
D/A conversion
SIPART DR22 6DR2210
C79000-G7476-C154-03
≤ 0,1 %
≤ 0,3 %
≤ 0,3 %
≤ 0.05 %
≤ 0.1 %/10 K
≤ 0.1 %/10 K
--1 to 35 V
+20 to 26 V
≤ 100 mA, short--circuit--proof
≤ 20 mA clocking
--1 to +35 V
≤ 4.5 V or open
≥ 13 V
≥ 27 kΩ
 35 V
≤ 1.5 V
+19 to 26 V
≤ 50 mA
≤ 80 mA, clocking
--1 to +35 V
adaptive 60 ms to 120 ms
(typical 80 ms)
Successive approximation per input
>120 conversions and averaging
of 20 or 16.67 ms
--4 to 110%
11 bit ≙ 0.06 %
≤ 0.2 %
≤ 0.2 %
≤ 0.2 %
≤ 0.05 %/10 K
≤ 0.1 %/10 K
See technical data "Analog inputs AA1 to
AA3"