The SIPART DR22 is designed with a high electromagnetic compatibility (EMC) and has a
high resistance to HF interference. In order to maintain this high operational reliability we
recommend that all inductances (e.g. relays, contactors, motors) installed in the vicinity of or
connected to the controllers should be assembled with suitable suppressors (e.g. RC com-
binations)!
7
12
11
10
9
8
4
Figure 2-1
Rear panel
SIPART DR22 6DR2210
C79000-G7476-C154-03
6
5
3
2
1
1 Slot 1
Main board
AE1 to AE3 (I/U)
AA1 bis AA3
BE1 to BE4
BA1 to BA8
24 V
L+, M
2 Slot 2
AE4 (I/U, R, P, T, V)
3 Slot 3
AE5 (I/U, R, P, T,V)
4 Slot 4
Serial interface
5 Slot 5
4BA 24 V+2BE
BA9 to BA12, BE5 to BE6
2BA relay
BA9, BA 10
5BE
BE5 to BE9
1AA
AA7
3AE
AE9 to AE11
3AA+3BA
AA7 to AA9, BE5 to BE7
6 Slot 6
4BA 24 V+2BE
BA13 to BA16, BE10 to BE11
2BA relay
BA13, BA14
5BE
BE10 to BE14
1AA(y-hold)
AA4
3AE
AE6 to AE8
3AA+3BE
AA4 to AA6, BE10 to BE12
7 PE conductor contact spring
8 Grounding screw
9 Mounting rail
(contained in scope of delivery of relay module
6DR2804--8A/B)
10 Mains voltage selection switch
11 Mains plug
12 Power supply unit
2 Installation
2.2 Electrical Connection