7.3 Powering the Panel

1 Connecting power, ALL front panel LED indicators
2 View the liquid crystal display. It should momentarily
version n.nna
Note: If faults are shown (other than the loss of loops on a
3 Externally isolate the AC mains supply at the third-

7.4 External Wiring

Refer to the appropriate module cable and wiring instructions
to identify the terminals for cable connections:
5.7.2 Base PCB Cables and Wiring. (Loops 1 & 2, Sounder
5.9.1 Loop interface PCB Cables and Wiring (Ioops 3 to 8).
5.10.1Enhanced Loop interface PCB Cables and Wiring
5.11.1 Isolated RS232 Interface PCB Cables and Wiring
5.12.1 Isolated RS485 Interface PCB Cables and Wiring

7.4.1 Introduction

There are five stages to commissioning the external
wiring:
a. Checking the loop wiring for continuity, reversed
b. Connecting the loop wiring to the panel.
c. Checking for faults after the loop wiring is connected
d. Checking the 24V auxiliary outputs wiring and
e. Checking the sounder circuits.
Note: The total length of the communications loop pair
45
should be extinguished with the exception of the green
'POWER' LED.
display the start-up message 'NOTIFIER ID3000
Version x.xx Intelligent Fire Detection System' where
'x.xx' is the software version number, together with
the version numbers of the Loop Interface Boards.
The display should then read 'Status: NORMAL (Date
and time)' unless faults are present on the system (if
the panel has already been configured, then faults
indicating the loss of all loop devices will be shown).
configured panel and battery failure), these must
be cleared before you proceed further with the
commissioning procedure.
party-supplied isolation unit.
ouputs 1 to 4, Auxiliary outputs 1 & 2, Fault Relay and
Fire relay outputs).
(Loops 3 to 8).
(RS232 output).
(RS485 output).
devices, short circuits and open circuits.
to the panel.
selecting the resettable status.
cannot exceed 2000 metres.