Honeywell Notifier ID3000 Series Installation & Commissioning Manual page 62

Fire control panels
Hide thumbs Also See for Notifier ID3000 Series:
Table of Contents

Advertisement

997-274-000-6, Issue 6
September 2009
ID3000 Series Installation & Commissioning Manual
1.1.6 Printer Faults
Printer Fault
Internal printer only. This fault may be an indication of a
paper jam or malfunction, no paper, or the printer may
be disconnected.
Note: The printer operation is only monitored if the printer
1.1.7 Other Hardware Faults
a. Fault 47 - CPU/Display hardware fault
b. Panel Key Stuck
c. Fault 48 - Base PCB/Expansion h/w fault
d. Aux. Output 1 Fault;
e. Fault 71 - Config. needs Expansion Card
f. Fault 72 - Config. needs RS485 Card
g. Fault 73 - Config. needs RS232 Card
h. Fault 74 - RS232\RS485\PRINTER Card displaced
A1 - 4
was functional at the last power-on.
Communications fault between the CPU and the
display.
Action: Change the CPU PCB assembly (PN: 020-
569) and/or the Display PCB/Membrane Keypad (PN:
020-571-XXX).
Change the Display PCB/Membrane Keypad
(PN: 020-571-XXX).
Change the Base PCB (PN: 020-568) or Extension
Chassis with Display Module Kit (PN: 020-559-XXX).
Aux. Output 2 Fault
This fault indicates a failure of the auxiliary drive
circuits and not the attached cables. Action: If the fault
is on either circuit, change the Base PCB (Kit
PN: 020-568).
This fault message can only appear when ID3000
panels are networked with earlier compatible panels.
This message is not applicable to the 'local' ID3000
Series panel. In cases where it is applicable, an
Extension Chassis with Display Module Kit
(PN: 020-559-XXX) is required.
Missing PCB - panel is configured for network but no
RS485 PCB is present. Fit Isolated RS485 Module
Kit (PN: 020-479) or change configuration.
Missing PCB - panel is configured for 3rd-party
protocol but no RS232 PCB is present (does not apply
to other modes of the port). Fit Isolated RS232 Module
Kit (PN: 020-478) or change configuration.
An attempt has been made to remove one of these
items while the panel is powered up. Remove power
before proceeding.