Honeywell Notifier ID3000 Series Installation & Commissioning Manual page 29

Fire control panels
Hide thumbs Also See for Notifier ID3000 Series:
Table of Contents

Advertisement

B
D
E
A C
Main chassis
wiring -
pre-wired
(see above)
997-274-000-6, Issue 6
September 2009
ID3000 Series Installation & Commissioning Manual
The illustration at left shows the DTP/Booster module
correctly located in the main chassis.
5.3.1.1 Main Chassis Wiring Connections
Once the DTP/Booster module is fitted to the main
chassis, the two wiring assemblies that are held by the
grommet should now be terminated on the Base PCB
connection sockets as follows:
a. The 10-way ribbon cable (A) is to be terminated at
b. The 4-wire power cable (C) is to be terminated at
Note: Connector (E) may not be fitted.
5.3.1.2 Other Wiring Connections
CAUTION: Before proceeding, refer to the cabling
instructions given in Section 3.1.
The following additional wiring must be connected:
a. If the DTP/Booster module is to be connected to an
b. Connect a suitable cable (supplied with the PSU)
c. If the DTP/Booster module is to be connected to an
d. Connect suitable (high-current) cables (if PSU is
e. CAUTION! If using an externally-mounted PSU, it
24
socket SK8 (B).
socket SK12 (D).
internally-mounted PSU (other than the Kit PSU3A), fit
the supplied ribbon cable between the DTP/Booster
connector (E) and the PSU's LED status indication output
connector. This connection is not used if the PSU is
mounted externally.
between the PSU Charger Inhibit connector (F) and the
equivalent connector on the PSU (on PSU assemblies
PN: 124-190 and 124-190-001, this connector is labelled
ALARM). Connect + to + and - to -.
externally-mounted PSU, connect a suitable cable
between the COMMON FAULT connector (G) and the
Normally Open and Common connections of the
equivalent connector on the PSU.
internal, use cables supplied with the PSU) between
the Power connector (H) and the power supply unit.
Connect + to + and - to - (may be labelled 0V).
is essential that an electrical safety earth
connection is made to the back box of the ID3000
panel. This connection should be routed with the other
PSU cables from the external battery box.