5.5.3 LEDs for up to 256 Zones

Where up to 256 zonal LEDs are required a kit is supplied
for use with the double-extended back box only. The two
Double-extension Chassis 256-Zone Status Kits contain
the following items:
a. Zone LED chassis (zones 1-128)
b. Zone LED chassis (zones 129-256)
c. Ribbon cables (x2)
d. Front cover earth lead
e. M4 x 16 SEM screws (x8)
f. Label inserts (2 per language variant) and
g. Cover.
The 256-Zone Status Indication Kit is simple to fit
providing the instructions below are followed.
Before attempting this procedure, make sure ALL
power to the control panel is disconnected.
With the back box (A) secured to the wall in its chosen
location and the front cover removed, fit each status
indication chassis (B) as follows:
Note: First, fit the chassis with zone LEDs 129-256 in
the lower back box position. Fit the chassis with
zone LEDs 1-128 in the upper position - after fitting
the front cover earth lead.
1 Locate the eight supplied M4 x 16 SEM screws (C) in
the back box holes (D) and insert them approximately
half way. Four screws are required for each chassis.
2 Ensure the factory-fitted internal ribbon cables are
satisfactorily connected to the extension chassis
connectors (i).
3 Fit one end of each loose-provided, inter-chassis
ribbon cable to the 'zones 1- 128' chassis as follows:
a. To the 'IN' connector (at iii), and
b. To the 'OUT' connector (at iv).
4 With each status indication chassis correctly
orientated, locate the keyholes onto four of the screws
with the threaded part in contact with the top flat of
the keyholes. Fit the 'zones 129-256' chassis first and
then the 'zones 1-128' chassis.
5 With the status indication chassis now located on the
back box, fit the other end of the two inter-chassis
ribbon cables. When fitting the 'zones 1-128' chassis,
connect the other end of the ribbon cable (from iv) to
the 'IN' connector (at ii) on the 'zones 129-256' chassis;
connect the other end of the second ribbon cable (from
iii) to the socket connector SK19 (at v) on the panel
Base PCB.
6 Connect the free end of the earthing lead (at vi) to the
blade terminals on the back box side wall.
7 When all cable connections have been made, use a
Posidriv No.2 screwdriver to secure both status
indication chassis.