Honeywell Notifier ID3000 Series Installation & Commissioning Manual page 27

Fire control panels
Hide thumbs Also See for Notifier ID3000 Series:
Table of Contents

Advertisement

WARNING!
Isolate mains power
before proceeding.
When terminating mains
leads, ensure that the
earth lead is longer than L
and N.
230 VAC,
230 VAC,
50 Hz
50 Hz
H
C
A
MF: 5A (T) 250V HRC
MF: 5A (T) 250V HRC
VIEW
X
230V
230V
997-274-000-6, Issue 6
September 2009
ID3000 Series Installation & Commissioning Manual
5.2.1.2 Mains and Safety Earth Wiring Connections
WARNING: Before proceeding, refer to the cabling
TRANSIT CABLE CLIP: Before proceeding,
CAREFULLY cut the cable clip that secures the ferrite
cable loop to the front of the back box. DO NOT cut the
cable clip that secures the mains cable to the side of the
back box.
The 230V ac mains input wiring (A) must be terminated
at the fused mains termination block (B), located in the
top right-hand corner of the ID3000 Series back box (C).
The PSU mains cable (D) is factory-fitted to the
termination block. Push the mains cable's connector (E)
into the socket at the top of the PSU3A. Pull tight the
cable clip at the side of the back box.
'X'
B
The safety earth is provided via a short factory-fitted lead
F
(F) from the mains termination block to a blade connector
(a.c.), 5A
(a.c.), 5A
at the right rear corner of the back box roof. All blade
connections to earth incorporate a locking barb. To make
a connection push the shrouded receptacle on to the earth
blade (1). To remove this connection, pull the shroud (2),
NOT the earth wire.
D
Using the wiring provided, make the following two earth
G
connections:
a. Between the PSU top plate and the back box (G).
E
b. Between the main chassis and the back box (H).
Connection to the batteries is made using the supplied
battery leads, which may have to be cut to the correct length.
Connection of the batteries (and thermistor) is made at a
four-way socket mounted close to the bottom of the PSU
assembly. Access is gained from underneath the PSU once
the main chassis is fitted to the back box.
For more information on connecting the batteries refer
to Section 7.5, Batteries.
22
instructions given in Section 3.1. Isolate
mains power. Note that fuse information is
given in Appendix 1 Section 1.2.

Hide quick links: