Honeywell Notifier ID3000 Series Installation & Commissioning Manual page 68

Fire control panels
Hide thumbs Also See for Notifier ID3000 Series:
Table of Contents

Advertisement

* Total system load is limited by the
available PSU output. Appendix 3, or the
Notifier Loop and Battery Calculator
Support Tool, should be used to ensure that
the system is NOT overloaded.
ID3000 Series Installation & Commissioning Manual
24 Volt DC Auxiliary Output Rating
Output voltage range:
Maximum load:
Quiescent:
Alarm:
Ripple Voltage:
Fuse rating:
Note: It is recommended that the auxiliary ouput should not
Loop Outputs (Two Standard and Six Optional)
Output voltage:
Maximum load:
Loop driver source
impedance:
Up to 198 loop devices (up to 99 sensors and 99 modules)
may be fitted to each analogue loop. For system limitations
refer to Section 4, Sensors and Modules.
The communication with devices on the loop uses the Notifier
'CLIP' protocol. Refer to Appendix 3, ID3000 System Design
Guide for a list of compatible devices and loading limitations.
RS232 Serial Port (Optional)
Isolation:
Baud rate:
Connector:
Max cable length:
RS485 Serial Port (Optional)
Isolation:
Baud rate:
Connector:
Maximum cable length: 3000m (minimum of 1mm
Programming
Configuration methods: Front panel key-pad;
Configuration access:
Repeaters
Refer to the Repeater manual for the specification.
A2 - 5
26 to 28 V
Refer to Appendix 3, ID3000
System Design Guide, or the
Notifier Loop and Battery Calculator
Support Tool.
150mA *
1A *
600mV
Electronic over-current protection
be used in the quiescent state other than to provide a
supply to drive ancillary devices' power indicators.
22.5 to 26.4V
0.5A*
3.8 ohms at 22.5V
Functional at 30V.
Software-selectable up to 9600
Baud.
Terminal block on RS232 PCB.
15m
Functional at 30V.
1200 Baud.
Terminal block on RS485 PCB.
screened cable recommended)
Off-line
Configuration Tool.
Keypad access is passcode-
protected (user-definable) for all
configuration options.
Refer to the ID3000 Series Panel
Configuration
997-506-000-X) for further information.
2
using
the
Off-line
Manual
(ref.
997-274-000-6, Issue 6
September 2009

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents