Analog Sensor Output - Nvoaivaluepct[ ]; Temperature Sensor Output - Nvoaitempp[ ]; Slow Digital Input - Nvoaiswitch[ ]; Temperature#2 Sensor Output - Nvoaitemp[ ] - Honeywell Excel 800 LION Installation And Commissioning Instructions

Table of Contents

Advertisement

Excel 800 LION
Default Service Type
The default service type of these variables is
unacknowledged.
Analog Sensor Output – nvoAiValuePct[ ]
This network variable output represents the percentage
level for the appropriate input, if configured for voltage input.
Valid Ranges for 0 ... 10 V Input
Value
< 0 V
0 V ... 10 V
> 10 V
Table 61 Analog input values: 0 ... 10 V
Valid Ranges for 2 ... 10 V Input
Value
< 1.5 V
1.5 V ... 2 V
2 V ... 10 V
> 10 V
Table 62 Analog input values: 2 ... 10 V
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
nvoAiValuePct = INVALID = 0x7FFF (=163.835 %)
The sensor failure behavior can be configured for 2 ... 10 V.
Representation
0 %
0 ... 100 %
100 %
Representation
Sensor break/short circuit
0 %
0 ... 100 %
100 %
Temperature Sensor Output – nvoAiTempP[ ]
This network variable output represents the temperature for
the appropriate input, if configured for temperature sensor,
except PT1000-2.
Range: see Table 43 and Table 44 on page 41.
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
nvoAiTempP = INVALID = 0x7FFF (= 327.67 ° C)
Slow Digital Input – nvoAiSwitch[ ]
This network variable output represents a slow digital input
connected to the universal input terminals.
Valid Range
Sensor
Enabled
Disabled
Not configured
Table 63 Slow digital input values
Temperature#2 Sensor Output – nvoAiTemp[ ]
This network variable output represents the temperature for
the appropriate input, if configured for temperature sensor if
configured for PT1000-2 sensor.
Range: see Table 43 and Table 44 on page 41.
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
nvoAiTemp = INVALID = 0xFFFF (= 6279.5 ° C)
63
Value
State
100 %
1
0 %
0
0 %
-1
EN1B-0375GE51 R0308