I/O Bus Switch S2; C-Bus Termination Switch S1; Memory - Honeywell Excel 800 LION Installation And Commissioning Instructions

Table of Contents

Advertisement

I/O Bus Switch S2

The CLLIONLC01 Controller Module features a 2-position
I/O Bus switch S2.
I/O Bus switch S2 must be set in accordance with the kind
of I/O modules connected to communication terminals
71, 72 and 75, 76 of the controller module.
Terminals 71, 72 and 75, 76 must be all connected either to
Panel Bus I/O modules or to L
The default setting is Panel.
Fig. 55
I/O Bus switch S2
Communication
L
W
Bus only
ON
ORKS
Panel Bus and L
W
ON
ORKS
L
W
B
modules connected to
ON
ORKS
US
terminals 11 .... 14 of the controller
Panel Bus connected to terminals 71, 72
or 75, 76 of the controller
Table 38 I/O Bus switch settings
EN1B-0375GE51 R0308
W
Bus I/O modules.
ON
ORKS
S2 setting
LON
Bus
Panel
Panel

C-Bus Termination Switch S1

The CLLIONLC01 Controller Module features a 3-position
C-Bus termination switch S1.
This switch must be set in accordance with the given C-Bus
configuration.
Fig. 56
C-Bus termination switch
Switch
Baud rate
setting S1
9.6k all
Up to 9600 baud (default setting)
76k mid
Up to 76800 baud without bus termination
Up to 76800 baud with bus termination
76k end
controller at the end of the C-Bus
Table 39 CLLIONLC01 C-Bus termination switch S1
settings

Memory

Memory
Size
SRAM
512 KB
Flash
2 MB
EPROM
128 KB
Table 40 CLLIONLC01 memory
Note
The CLLIONLC01 Controller Module does not contain a
battery. RAM (data and realtime clocktime) is buffered for
3 days by a super capacitor.
38
Excel 800 LION
Usage
For controller application,
modem trend and firmware
RACL application: 128 KB
Total application: 192 KB
Firmware (1 MB) and
application (1 MB) storage
For bootstrap loader

Hide quick links:

Advertisement

Table of Contents