Analog Output Modules

Types of Analog Output Modules, Terminal Socket

Type
Description
CLIOP822A
Panel Bus analog
output module
CLIOPR822A Panel Bus analog
output module with
manual overrides
CLIOL822A
L
W
ON
ORKS
output module
CLIOLR822A L
W
ON
ORKS
output module with
manual overrides
XS821-22
Terminal socket
Table 45 Excel 800 LION analog output modules

Features

• 8 analog outputs;
can also be configured per output as binary outputs
(0 ... 10 V, 2 ... 10 V, ON/OFF, or floating)
• Corresponding output status LEDs (red)
• ...R822: 8 manual overrides, see figure below
Fig. 64
CLIOP822A Analog Output Module with terminal
socket
Legend
1
Service button S1
2
Hex switch S2
3
Manual overrides
4
Output LEDs
5
Service LED
6
Power LED
Housing
Light gray
Light gray
Bus analog
Dark gray
Bus analog
Dark gray
Light gray
Functionality of service LED and power LED: see Table 74
to Table 76 on page 72 and following.
In the event of communication problems, the analog outputs
will move to the safety positions you have configured in
CARE, see analog output point description in the CARE –
User Guide, 74-5587/EN2B-0182GE51.

Terminals

Fig. 65
Terminal assignment and internal connections of
the analog output modules
Ter-
Signal
minal
71, 75
COM a
72, 76
COM b
73, 77
24 V~
74, 78
24 V~0
1...8
AO1...AO8 Analog outputs 1...8
9...18
GND
21, 22
N.C.
25, 26
Table 46 Description of the analog output module terminals
Notes
• Shield connection to be used for shielded I/O cables only.
It is not allowed to connect a L
L
W
requires a resistor and a capacitor.
ON
ORKS
• If additional shield terminals are needed, the
XS814 Auxiliary Terminal Package can be installed.
45
COMMENT
2-wire communication bus
(LON/Panel Bus)
2-wire communication bus
(LON/Panel Bus)
Power supply
Power supply
Ground. All grounds are connected
internally to each other
Do not use!
Shield connection (functional earth),
internally connected to the DIN rail
W
shield, since
ON
ORKS
EN1B-0375GE51 R0308