Additional relay outputs by using option module MCB 105.
5.5.5. Parallel Connection of Motors
The frequency converter can control several parallel-connected motors.
The total current consumption of the motors must not exceed the rated
output current I
for the frequency converter.
INV
NB!
When motors are connected in parallel, par. 1-29 Au-
Motor Adaptation (AMA)
tomatic
Problems may arise at start and at low RPM values if motor sizes are
widely different because small motors' relatively high ohmic resistance in
the stator calls for a higher voltage at start and at low RPM values.
The electronic thermal relay (ETR) of the frequency converter cannot be
used as motor protection for the individual motor of systems with parallel-
connected motors. Provide further motor protection by e.g. thermistors
in each motor or individual thermal relays. (Circuit breakers are not suit-
able as protection).
cannot be used.
®
MG.20.N4.02 - VLT