General Specifications and ...
Adjustable frequency drive
Typical shaft output [kW]
Typical shaft output [hp]
IP54 frame
Max. cable size in terminals (line power, motor)
2
[mm
/AWG]
Output current
104 °F [40 °C] ambient temperature
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x440–480 V) [A]
Intermittent (3x440–480 V) [A]
Max. input current
Continuous (3x380-440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x440–480 V) [A]
Intermittent (3 x 440–480 V) [A]
Max. electrical fuses
8
8
Estimated power loss [W], Best case/typical
Weight enclosure IP54 [kg]
Efficiency [%], Best case/Typical
Output current
122 °F [50 °C] ambient temperature
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x440–480 V) [A]
Intermittent (3x440–480 V) [A]
Table 8.7 P18K–P90K
1) At rated load conditions
112
Design Guide
P18K
18.5
25
I4
16/6
37.0
40.7
34.0
37.4
35.2
38.7
29.3
32.2
1)
412/
456
13.8
1)
98.1/
97.9
33.0
36.3
30.0
33.0
Danfoss A/S © Rev. 2014-01-14 All rights reserved.
P22K
P30K
P37K
P45K
22.0
30.0
37.0
45.0
30.0
40.0
50.0
60.0
I6
I6
I6
35/2
35/2
35/2
50/1
44.0
61.0
73.0
90.0
48.4
67.1
80.3
99.0
40.0
52.0
65.0
80.0
44.0
57.2
71.5
88.0
41.8
57.0
70.3
84.2
46.0
62.7
77.4
92.6
36.0
49.2
60.6
72.5
39.6
54.1
66.7
79.8
496
734
995
840
27
27
27
98.0
97.8
97.6
98.3
35.2
48.8
58.4
63.0
38.7
53.9
64.2
69.3
32.0
41.6
52.0
56.0
35.2
45.8
57.2
61.6
P55K
P75K
P90K
55.0
75.0
90.0
70.0
100.0
125.0
I7
I7
I8
I8
50/1
95/(3/0) 120/(4/0)
106.0
147.0
177.0
116.6
161.7
194.7
105.0
130.0
160.0
115.5
143.0
176.0
102.9
140.3
165.6
113.1
154.3
182.2
88.6
120.9
142.7
97.5
132.9
157.0
1099
1520
1781
45
45
65
65
98.2
98.1
98.3
74.2
102.9
123.9
81.6
113.2
136.3
73.5
91.0
112.0
80.9
100.1
123.2
MG18C522
Need help?
Do you have a question about the VLT HVAC Basic Drive FC 101 and is the answer not in the manual?
Questions and answers