Parameter List

For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel. For details of parameters, refer to the instruction manual.
POINT
 Only simple mode parameters are displayed by the initial setting of Pr.160 Extended function display selection. Set
Pr.160 Extended function display selection as required.
 To use the inverter under IPM motor control, refer to page 81.
Pr.160
9999
Only the simple mode parameters can be displayed.
(initial value)
0
Simple mode and extended mode parameters can be displayed.
Simple mode parameter
Parameter
Name
Number
0
Torque boost
1
Maximum frequency
2
Minimum frequency
3
Base frequency
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting (low
6
speed)
7
Acceleration time
8
Deceleration time
Electronic thermal O/L
9
relay
Operation mode
79
selection
Terminal 2 frequency
125
setting gain frequency
Terminal 4 frequency
126
setting gain frequency
Extended function
160
display selection
IPM parameter
998
initialization
Automatic parameter
999
setting
24
Remarks
Initial
Unit
Range
Value
6%/4%/
0.1%
0 to 30%
3%/2%
0.01Hz
120Hz
0 to120Hz
0.01Hz
0Hz
0 to120Hz
0.01Hz
60Hz
0 to 400Hz
0.01Hz
60Hz
0 to 400Hz
0.01Hz
30Hz
0 to 400Hz
0.01Hz
10Hz
0 to 400Hz
0.1s
5s/15s
0 to 3600s
0.1s
10s/30s
0 to 3600s
Rated
0.01A
inverter
0 to 500A
current
0, 1, 2, 3, 4, 6,
1
0
7
0.01Hz
60Hz
0 to 400Hz
0.01Hz
60Hz
0 to 400Hz
1
9999
0, 9999
0, 1, 12, 101,
1
0
112
10, 20, 21,
1
9999
9999
Application
Use this parameter to increase starting
torque under V/F control. Use this when a
loaded motor cannot be driven and the
warning [OL] occurs, then the inverter trips
with [OC1] under V/F control.
 Initial value depends on the inverter capacity.
(0.75K or less/1.5K to 3.7K/5.5K, 7.5K/11K, 15K)
Use this parameter to set the upper limit for
the output frequency.
Use this parameter to set the lower limit for
the output frequency.
Use this parameter when the rated motor
frequency is 50Hz.
Check the rating plate of the motor.
Use these parameters to change among pre-
set operation speeds with the terminals. The
speeds are pre-set with parameters.
Use these parameters to set the
acceleration/deceleration time.
 Initial value depends on the inverter capacity.
(7.5K or less/11K, 15K)
With this parameter, the inverter protects the
motor from heat.
Set the rated motor current.
Use this parameter to select the source of
start command and frequency setting.
Use this parameter to change the frequency
at the maximum potentiometer setting (5V in
the initial setting)
Use this parameter to change the frequency
at the maximum current input (20mA in the
initial setting)
Parameter which can be read from the
operation panel and parameter unit can be
restricted.
By performing IPM parameter initialization,
IPM motor control is selected and the
parameters, which are required to drive an
IPM motor, are changed.
Parameter settings are changed as a batch.
Those include communication parameter
settings for the Mitsubishi's human machine
interface (GOT) connection and the
parameter setting for the rated frequency
settings of 50Hz/60Hz.
Refer
to
page
33
33
33
33
34
34
43
46
46
47
80
56