Connection Example

AC power supply
Use within the permissible power supply
specifications of the inverter. To ensure
safety, use a moulded case circuit breaker,
earth leakage circuit breaker or magnetic
contactor to switch power ON/OFF.
(Refer to page 11)
Molded case circuit breaker (MCCB),
earth leakage circuit breaker (ELB),
or fuse
The breaker must be selected carefully
since an inrush current flows in the
inverter at power on.
(Refer to page 68)
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will
cause the inverter life to be shortened.
(Refer to page 68)
AC reactor (FR-HAL)
(Refer to page 60)
Noise filter (ferrite core)∗
(FR-BSF01, FR-BLF)
(Refer to page 62)
* Not necessary if Filterpack (FR-BFP2) is used.
High power factor
converter (FR-HC2)
(Refer to page 66)
NOTE
 The life of the inverter is influenced by surrounding air temperature. Use the product within the permissible
surrounding air temperature. This must be noted especially when the inverter is installed in an enclosure.
(Refer to chapter 1 of
 Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main
circuit to protect them from noise. (Refer to page 17)
 Do not install a power factor correction capacitor, surge suppressor or noise filter (capacitor) on the inverter output
side. This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above
devices are connected, immediately remove them.
 Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. In this case, install the FR-BIF optional EMC filter
(capacitor) (for use in the input side only) or FR-BSF01 or FR-BLF noise filter (ferrite core) to minimize interference.
(Refer to chapter 3 of
 Refer to the Instruction Manual of each option and peripheral devices for details of peripheral devices.
 An IPM motor cannot be driven by the commercial power supply.
 An IPM motor is a motor with permanent magnets embedded inside. High voltage is generated at the motor terminals while the
motor is running. Before closing the contactor at the output side, make sure that the inverter power is ON and the motor is stopped.
10
Parameter unit
(Refer to page 22)
(FR-PU07)
DC reactor (FR-HEL)∗
Inverter
FR-F700PJ
(Refer to page 61)
P/+
P1
Noise filter
(capacitor)
(FR-BIF)
(Refer to
page 61)
Brake unit
(FR-BU2)
Power regeneration
Resistor unit (FR-BR)
common converter
Discharging resistor (GZG, GRZG)
(Refer to page 63)
(FR-CV)
(Refer to page 65)
the Instruction Manual (Applied))
the Instruction Manual (Applied))
Enclosure surface operation
panel (FR-PA07)
(Refer to page 60)
RS-485 RS-232C
Converter
Inverter (FR-F700PJ)
Filterpack (FR-BFP2)
The FR-F7
0PJ-
F Filterpack
model has "F" at the end of its
model name. An inverter and a
Filterpack are enclosed with this series.
P/+
PR
IM connection
U
V W
Earth (Ground)
R/L1 S/L2T/L3
General-
purpose
motor
P/+ N/-
Earth
(Ground)
Devices connected
to the output
Do not install a power
factor correction capacitor,
PR
P/+
surge suppressor or noise filter (capacitor) on the output
P/+
side of the inverter. When installing a molded case
PR
circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the
molded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground)
the motor and inverter. For reduction of induction noise
from the power line of the inverter, it is recommended
to wire the earth (ground) cable by returning it to the
earth (ground) terminal of the inverter.
RS-232C - RS-485 converter is
required when connecting to PC
with RS-232C interface.
Brake resistor
(FR-ABR, MRS type, MYS type)
(Refer to page 62)
IPM connection
U V W
Noise filter
(ferrite core)
(FR-BSF01,
FR-BLF)
(Refer to page 62)
Contactor
Example) No-fuse
switch (DSN type)
Install a contactor in
an application where
the IPM motor is
driven by the load
even at power-OFF
of the inverter. Do
not open or close
the contactor while
the inverter is
running (outputting).
Dedicated IPM
motor (MM-EFS,
MM-EF)
(Refer to page 77)
Earth
(Ground)