Mitsubishi Electric FR-F700PJ Series Manual page 40

Hide thumbs Also See for FR-F700PJ Series:
Table of Contents

Advertisement

57, 162, 611
Automatic restart after instantaneous
power failure/flying start under IPM
motor control
Pr.57 Restart coasting time
Pr.162 Automatic restart after instantaneous power failure selection
Pr.611 Acceleration time at a restart
The inverter can be restarted without stopping the IPM motor in
the following cases:
 When power comes back ON during inverter driving after an
instantaneous power failure
 When the motor is coasting at start
For V/F control and General-purpose magnetic flux vector control,
refer to the previous page.
Pr.
Setting
Number
Range
0
0.1 to 5s
57
9999
(initial value)
0, 1
162
(initial value)
10, 11
0 to 3600s
611
9999
(initial value)
Automatic restart operation selection (Pr.162)
The inverter smoothly starts after detecting the motor speed
(frequency search) upon power restoration.
During reverse rotation, the inverter can be restarted smoothly as
the direction of rotation is detected.
Power supply
(R/L1,S/L2,T/L3)
Motor
speed N (r/min)
Inverter output
frequency f (Hz)
Inverter output
voltage E (V)
Coasting
time (Pr. 57)
∗ The output shut off timing differs
according to the load condition.
40
When setting parameters, refer to the instruction manual (applied) and understand instructions.
IPM
IPM
IPM
Description
No waiting time
Set the waiting time for inverter-triggered
restart after an instantaneous power
failure.
No restart
With frequency search
Frequency search at every start
Set the acceleration time that takes to
reach Pr.20 Acceleration/deceleration
reference frequency setting at a restart.
Acceleration time for restart is the normal
acceleration time (e.g. Pr. 7).
Instantaneous (power failure) time
Speed
+
detection time
Acceleration time
at a restart
(Pr. 611 setting)
59
Remote setting function
Pr.59 Remote function selection
Even if the operation panel is located away from the enclosure, you
can use contact signals to perform continuous variable-speed
operation, without using analog signals.
By merely setting this parameter, you can use the acceleration,
deceleration and setting clear functions of the remote speed setter
(FR-FK).
Pr.59 setting
RH, RM, RL signal
function
0 (initial value)
Multi-speed setting
1
Remote setting
2
Remote setting
3
Remote setting
0Hz
0
Acceleration
ON
ON
(RH)
Deceleration
(RM)
ON
Clear (RL)
Forward rotation
(STF)
ON
Power supply
 External running frequency (other than multi-speed operation) or PU
running frequency
60
Energy saving control selection
Pr.60 Energy saving control selection
Without a fine parameter setting, the inverter automatically
performs energy saving operation.
This operation is optimum for fan and pump applications.
Pr.60 setting
0 (initial value)
Normal operation mode
Optimum excitation control mode
The Optimum excitation control mode is a control
9
system which controls excitation current to improve
the motor efficiency to maximum and determines
output voltage as an energy saving method. 
 Since output voltage is controlled, output current may slightly increase.
Description
Frequency setting
storage function
Used
Not used
Not used (Turning STF/
STR off clears
remotely-set
frequency.)
When Pr. 59 = 1, 2
When Pr. 59 = 1
When Pr. 59 = 3
When Pr. 59 = 2, 3
Time
ON
ON
ON
ON
ON
ON
ON
V/F
V/F
V/F
Description