Item
Automatic restart after
No startup waiting time.
instantaneous power
Using the regeneration avoidance function together
is recommended.
failure
Startup delay
Startup delay of about 0.1s for initial tuning.
Driving by the
Not available.
commercial power
Never connect an IPM motor to the commercial
power supply.
supply
While the motor is coasting, potential is generated
Operation during
across motor terminals.
coasting
Before wiring, make sure that the motor is stopped.
FR-F740PJ-0.4K.............................. 50m or shorter
Maximum motor wiring
FR-F720PJ-0.4K to 15K,
length
FR-F740PJ-0.75K to15K ................. 100m or shorter
NOTE
 No slippage occurs with an IPM motor because of its characteristic.
If an IPM motor, which took over a general-purpose motor, is driven at the same speed as for the general-purpose
motor, the running speed of the IPM motor becomes faster by the amount of the general-purpose motor's slippage.
Adjust the speed command to run the IPM motor at the same speed as the general-purpose motor, as required.
IPM motor control
General-purpose motor control
Startup waiting time exists.
No startup delay.
Can be driven by the commercial power supply.
While the motor is coasting, no potential is generated
across motor terminals.
500m or shorter in total