892 to 899
Energy saving monitor
Pr.892 Load factor
Pr.893 Energy saving monitor reference (motor capacity)
Pr.894 Control selection during commercial power-supply operation
Pr.895 Power saving rate reference value
Pr.897 Power saving monitor average time
Pr.898 Power saving cumulative monitor clear
Pr.899 Operation time rate (estimated value)
From the power consumption estimated value during
commercial power supply operation, the energy saving effect
by use of the inverter can be monitored/output.
The following provides the items that can be monitored by the power
saving monitor (Pr. 52, Pr. 54 = "50").
(Only power saving and average power saving value can be output
to Pr. 54 (terminal FM))
Energy
Saving
Description and Formula
Monitor
Item
Difference between the estimated value of
power necessary for commercial power supply
operation and the input power calculated by the
Power
saving
inverter
Power during commercial power supply
operation - input power monitor
Ratio of power saving on the assumption that
power during commercial power supply
operation is 100%
Power saving
Power during commercial
Power
power supply operation
saving rate
Ratio of power saving on the assumption that
Pr. 893 is 100%
Power saving
Pr.893
Average value of power saving amount per
Power
hour during predetermined time (Pr. 897)
saving
 (Power saving t)
average
value
Pr.897
Ratio of average power saving value on the
assumption that the value during commercial
power supply operation is 100%
 (Power saving rate t)
Power
saving rate
Pr.897
average
Ratio of average power saving value on the
value
assumption that Pr. 893 is 100%
Power saving average value
Pr.893
Power
saving
Power saving average value represented in
charge
terms of charge
Power saving average value  Pr.896
average
value
The following gives the items which can be monitored by the cumulative
power saving monitor (Pr. 52 = "51").
(The cumulative power monitor data digit can be shifted to the right by the
number set in Pr. 891 Cumulative power monitor digit shifted times.)
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.896 Power unit cost
Increments
0.01kW
 100
0.1%
 100
0.01kWh
 100
0.1%
 100
0.01
Energy
Saving
Description and Formula
Monitor
Item
Power
Power saving is added up per hour.
saving
 (Power saving t)
amount
Power saving amount represented in terms of
Power cost
charge
savings
Power saving amount  Pr.896
Estimated value of annual power saving
Annual
amount
power
Power saving amount
saving
Operation time during
amount
power saving totalization
Annual
Annual power saving amount represented in
power cost
terms of charge
Annual power saving amount  Pr.896
savings
C0(900)
Adjustment of terminal FM (calibration)
C0(Pr.900) FM terminal calibration
The operation panel and parameter unit can be used to calibrate
the full scales of the terminals FM.
FM terminal calibration (C0(Pr.900))
The terminal FM is preset to output pulses. By setting the
Calibration parameter C0 (Pr. 900), the meter connected to the
inverter can be calibrated by parameter setting without use of a
calibration resistor.
Using the pulse train output of the terminal FM, a digital display
can be provided by a digital counter. The monitor value is 1440
pulses/s output at the full-scale value of Pr. 54 FM terminal function
selection.
Indicator
1mA full-scale
analog meter
1mA
FM
(+)
(-)
Calibration
resistor ∗
8VDC
SD
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr. 55 (frequency monitor)
Set with Pr. 56 (current monitor)
 Not needed when the operation panel or parameter unit (FR-PU07) is
used for calibration. Use a calibration resistor when the indicator
(frequency meter) needs to be calibrated by a neighboring device
because the indicator is located far from the inverter. However, the
frequency meter needle may not deflect to full-scale if the calibration
resistor is connected. In this case, perform calibration using the
operation panel or parameter unit.
C2(902) to C7(905),
Refer to the section about Pr.125
C22(922) to C25(923)
Refer to the section about Pr.127
C42(934) to C45(935)
990
Buzzer control of the operation panel
Pr.990 PU buzzer control
You can make the buzzer "beep" when you press key of the
parameter unit (FR-PU07).
Pr.990 setting
0
Without buzzer
1 (initial value)
With buzzer
Increments
0.01kWh
0.01
0.01kWh
Pr.899
 24 365
100
0.01
(Digital indicator)
1440 pulses/s(+)
(-)
FM
T1
SD
T2
Description
55