Specify operation mode at power on (Pr.340)
When power is switched on or when power comes back on after
instantaneous power failure, the inverter can be started up in the
Network operation mode.
After the inverter has started up in the Network operation mode,
parameter write and operation can be performed from a program.
Set this mode for communication operation using the inverter RS-
485 communication.
You can set the operation mode at power on (reset) according to
the Pr. 79 and Pr. 340 settings.
Operation mode at
Pr.340
Pr.79
Power On, Power
setting
setting
Restoration, Reset
0
(initial
As set in Pr.79.
value)
0
NET operation mode
1
PU operation mode
2
NET operation mode
External/PU combined
3, 4
1
operation mode
6
NET operation mode
X12 (MRS) signal ON
....... NET operation
mode
7
X12 (MRS) signal OFF
....... External
operation mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
External/PU combined
3, 4
10
operation mode
6
NET operation mode
External operation
7
mode
 The operation mode cannot be switched directly between the PU
operation mode and Network operation mode.
 Operation mode can be changed between the PU operation mode and
Network operation mode with
X65 signal.
44
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Operation Mode
Switchover
Can be switched to
external, PU or NET
operation mode

Fixed to PU operation
mode
Can be switched to
external or NET operation
mode
Switching to PU operation
mode disabled
Operation mode
switching disabled
Can be switched to
external, PU or NET
operation mode with
operation continued
Can be switched to
external, PU or NET
operation mode

Fixed to External
operation mode (Forcibly
switched to External
operation mode.)
Can be switched to PU or
NET operation mode

Fixed to PU operation
mode
Fixed to NET operation
mode
Operation mode
switching is disallowed
Can be switched to PU or
NET operation mode with
operation continued

Fixed to External
operation mode (Forcibly
switched to External
operation mode.)
key of the operation panel and
80, 71
General-purpose magnetic flux vector
control
GP
GP
GP
MFVC
MFVC
MFVC
Pr.80 Motor capacity
Large starting torque and low speed torque are available with
General-purpose magnetic flux vector control.
Parameter
Setting
Number
Range
By selecting a standard motor or
0, 1, 3, 13, 23,
constant-torque motor, thermal
71
40, 43, 50, 53,
characteristic and motor constants of
120, 210
each motor are set.
0.4 to 15kW
Applied motor capacity.
80
9999
V/F control
(initial value)
If the following conditions are not satisfied, select V/F control since
malfunction such as insufficient torque and uneven rotation may
occur.
The motor capacity should be equal to or one rank lower than the
inverter capacity.
Motor to be used is any of Mitsubishi standard motor (SF-JR
0.4kW or higher), high efficiency motor (SF-HR 0.4kW or higher)
or Mitsubishi constant-torque motor (SF-JRCA 4P, SF-HRCA
0.4kW to 15kW). When using a motor other than the above (other
manufacturer's motor), perform offline auto tuning without fail.
Single-motor operation (one motor run by one inverter) should be
performed.
The wiring length from inverter to motor should be within 30m.
(Perform offline auto tuning in the state where wiring work is
performed when the wiring length exceeds 30m.)
Permissible wiring length between inverter and motor differs
according to the inverter capacity and setting value of Pr. 72 PWM
frequency selection (carrier frequency). Refer to page 73 for the
permissible wiring length.
Pr.71 Applied motor
Description