Directional Underpower Protection Guppdup (37) - ABB RELION 670 Series Applications Manual

Phasor measurement unit version 2.1 ansi
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 511 364-UUS A
Imult : Enter the number of lines in case the protection function is applied on multiple parallel lines
sharing one CT.
IRef : Reference, steady state current, given in % of IBase that will give a steady state (end)
temperature rise
allowed for the line/cable under emergency operation (a few hours per year).
TRef : Reference temperature rise (end temperature) corresponding to the steady state current
IRef . From cable manuals current values with corresponding conductor temperature are often
given. These values are given for conditions such as ground temperature, ambient air
temperature, way of laying of cable and ground thermal resistivity. From manuals for overhead
conductor temperatures and corresponding current is given.
Tau : The thermal time constant of the protected circuit given in minutes. Please refer to
manufacturers manuals for details.
TripTemp : Temperature value for trip of the protected circuit. For cables, a maximum allowed
conductor temperature is often stated to be 190°F (88°C). For overhead lines, the critical
temperature for aluminium conductor is about 190-210°F (88-99°C). For a copper conductor a
normal figure is 160°F (71°C).
AlarmTemp : Temperature level for alarm of the protected circuit. ALARM signal can be used as a
warning before the circuit is tripped. Therefore the setting shall be lower than the trip level. It shall
at the same time be higher than the maximum conductor temperature at normal operation. For
cables this level is often given to 150°F (66°C). Similar values are stated for overhead lines. A
suitable setting can be about 60°F (16°C) below the trip value.
ReclTemp : Temperature where lockout signal LOCKOUT from the protection is released. When the
thermal overload protection trips a lock-out signal is activated. This signal is intended to block
switch in of the protected circuit as long as the conductor temperature is high. The signal is
released when the estimated temperature is below the set value. This temperature value should be
chosen below the alarm temperature.
8.6

Directional underpower protection GUPPDUP (37)

8.6.1
Identification
Function description
Directional underpower protection
8.6.2
Application
The task of a generator in a power plant is to convert mechanical energy available as a torque on a
rotating shaft to electric energy.
Application manual
TRef . It is suggested to set this current to the maximum steady state current
IEC 61850
identification
GUPPDUP
IEC 60617
ANSI/IEEE C37.2
identification
device number
37
P <
2
SYMBOL-LL V2 EN-US
Section 8
Current protection
SEMOD156693-1 v4
SEMOD158941-2 v4
SEMOD151283-4 v5
137

Advertisement

Table of Contents
loading

This manual is also suitable for:

Res670

Table of Contents