1MRK 511 364-UUS A
AngleROA : Angle value, given in degrees, to define the angle sector of the directional function,
shown in Figure 49.
NumPhSel : Number of phases, with high current, required for operation. The setting possibilities
1 out of 3 , 2 out of 3 and 3 out of 3 . The default setting is 1 out of 3 .
are:
PUMinOpPhSel : Minimum current setting level for releasing the directional start signals in % of IB .
This setting should be less than the lowest step setting. The default setting is 7% of
2ndHarmStab : Operate level of 2nd harmonic current restrain set in % of the fundamental current.
The setting range is
ANSI09000636 V1 EN-US
Figure 49: Directional function characteristic
1.
RCA = Relay characteristic angle
2.
ROA = Relay operating angle
3.
Reverse
4.
Forward
Application manual
5 - 100 % in steps of 1%. The default setting is 20%.
3
2
V
ref
1
2
4
I
dir
ANSI09000636-1-en.vsd
Section 8
Current protection
IB .
111