Section 6
6.1
Protocol reporting via IEEE 1344 and C37.118
PMUREPORT
6.1.1
Identification
Function description
Protocol reporting via IEEE 1344 and
C37.118
6.1.2
Application
The phasor measurement reporting block moves the phasor calculations into an IEEE C37.118
and/or IEEE 1344 synchrophasor frame format. The PMUREPORT block contains parameters for
PMU performance class and reporting rate, the IDCODE and Global PMU ID, format of the data
streamed through the protocol, the type of reported synchrophasors, as well as settings for
reporting analog and digital signals.
The message generated by the PMUREPORT function block is set in accordance with the IEEE
C37.118 and/or IEEE 1344 standards.
There are settings for Phasor type (positive sequence, negative sequence or zero sequence in case
of 3-phase phasor and L1, L2 or L3 in case of single phase phasor), PMU's Service class (Protection
or Measurement), Phasor representation (polar or rectangular) and the data types for phasor data,
analog data and frequency data.
Synchrophasor data can be reported to up to 8 clients over TCP and/or 6 UDP group clients for
multicast or unicast transmission of phasor data from RES670. More information regarding
synchrophasor communication structure and TCP/UDP configuration is available in section
C37.118 Phasor Measurement Data Streaming Protocol
Multiple PMU functionality can be configured in RES670, which can stream out same or different
data at different reporting rates or different performance (service) classes. There are 2 instances
of PMU functionality available in RES670. Each instance of PMU functionality includes a set of PMU
reporting function blocks tagged by the same instance number (1 or 2). As shown in the following
figures, each set of PMU reporting function blocks includes PMUREPORT, PHASORREPORT1-4,
ANALOGREPORT1-3, and BINARYREPORT1-3 function blocks. In general, each instance of PMU
functionality has 32 configurable phasor channels (PHASORREPORT1–4 blocks), 24 analog channels
(ANALOGREPORT1-3 blocks), and 28 digital channels (24 digital-report channels in
BINARYREPORT1-3 and 4 trigger-report channels in PMUREPORT function block). Special rules shall
be taken into account in PCM600 for Application Configuration and Parameter Settings of multiple
PMUREPORT blocks. These rules are explained in RES670 Application Manual in section
Report Function Blocks Connection
Application manual
Wide area measurement system
IEC 61850
identification
PMUREPORT
Rules.
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Configuration.
Section 6
Wide area measurement system
GUID-0C45D2FA-1B95-4FCA-B23B-A28C2770B817 v1
GUID-0090956B-48F1-4E8B-9A40-90044C71DF20 v1
GUID-8DF29209-252A-4E51-9F4A-B14B669E71AB v2
PMU
77