Section 14
Control
14.6.2

Application

Single command, 16 signals (SINGLECMD) is a common function and always included in the IED.
The IEDs may be provided with a function to receive commands either from a substation
automation system or from the local HMI. That receiving function block has outputs that can be
used, for example, to control high voltage apparatuses in switchyards. For local control functions,
the local HMI can also be used. Together with the configuration logic circuits, the user can govern
pulses or steady output signals for control purposes within the IED or via binary outputs.
Figure
72
logic circuit to control a high-voltage apparatus. This type of command control is normally carried
out by sending a pulse to the binary outputs of the IED. Figure
open breaker operation is performed in a similar way but without the synchro-check condition.
Close CB1
ANSI04000206 V2 EN-US
Figure 72: Application example showing a logic diagram for control of a circuit breaker via
Figure
73
Disabled signals. Here, the output is used to control built-in functions or external devices.
196
shows an application example of how the user can connect SINGLECMD via configuration
Single
command
function
SINGLECMD
CMDOUTy
OUTy
configuration logic circuits
and figure
74
show other ways to control functions, which require steady Enabled/
Configuration logic circuits
User-
AND
defined
conditions
Synchro-
check
en04000206_ansi.vsd
1MRK 511 364-UUS A
72
shows a close operation. An
Application manual