ABB RELION 670 Series Applications Manual page 84

Phasor measurement unit version 2.1 ansi
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 6
Wide area measurement system
Figure
30
instance has 4 predefined binary input signals corresponding to the Bits 03-00: Trigger Reason
defined in STAT field of the Data frame in IEEE C37.118.2 standard. These are predefined inputs for
Frequency Trigger, Rate of Change of Frequency trigger, Magnitude High and Magnitude Low
triggers.
IEC140000118 V1 EN-US
Figure 30: Multiple instances of PMUREPORT function block
Figure
31
visible in the bottom of each function block. For each instance, there are four separate
PHASORREPORT blocks including 32 configurable phasor channels (8 phasor channels in each
PHASORREPORT block). Each phasor channel can be configured as a 3-phase (symmetrical
components positive/negative/zero) or single-phase phasor (L1/L2/L3).
IEC140000119 V1 EN-US
Figure 31:
Figure
32
in the bottom of each function block. For each instance, there are three separate ANALOGREPORT
blocks capable of reporting up to 24 Analog signals (8 Analog signals in each ANALOGREPORT
block). These can include for example transfer of active and reactive power or reporting the
milliampere input signals to the PDC clients as defined in IEEE C37.118 data frame format.
78
shows both instances of the PMUREPORT function block. As seen, each PMUREPORT
shows both instances of the PHASORREPORT function blocks. The instance number is
Multiple instances of PHASORREPORT blocks
shows both instances of ANALOGREPORT function blocks. The instance number is visible
1MRK 511 364-UUS A
Application manual