3.1.1 EMC standards

When the programmable controller is installed following the directions given in this
manual its EMC performance is compliant to the following standards and levels as
required by the EMC directive.
Specifications
EN55011 *2
Radiated noise
EN61000-6-4
(2001)
EN55011 *2
Conduction noise
EN61000-4-2 *2
Static electricity
immunity
EN61000-4-4 *2
First transient burst
noise
EN61131-2/A
12 (2000)
EN61000-4-12 *2
Damped oscillatory
wave
EN61000-4-3 *2
Radiated
electromagnetic field
EN61000-6-2
EN61000-4-6 *2
(2001)
Conduction noise
1: QP: Quasi-peak value, Mean: Average value
2: The programmable controller is an open type device (device installed to
another device) and must be installed in a conductive control panel.
The tests for the corresponding items were performed while the
programmable controller was installed inside the control panel.
Test Item
Measure the emission
released by the product.
Measure the emission
released by the product to
the power line.
Immunity test by applying
static electricity to the
module enclosure.
Immunity test by applying
burst noise to the power line
and signal line.
Immunity test in which a
damped oscillatory wave is
superimposed on the power
line.
Immunity test by applying a
radiated electric field to the
product.
Immunity test by inducting an
electromagnetic field in the
power line signal line.
Test Description
4
Standard Values
30M-230 M Hz QP: 30dBμ V/m
(30m measurement) *1
230M-1000MHz QP: 37dBμ V/m
(30m measurement) *1
150k-500kHz QP: 79dB,
Mean: 66dB*1
500k-30MHz QP:73dB,
Mean: 60dB *1
4kV contact discharge
8kV air discharge
2kV Power line
1kV Signal line
1kV
10V/m, 26-1000MHz
10 V/ms, 0.15-80MHZ, 80% AM
modulation@1kHz