Error
Error
Code
Message
(D9008)
"INSTRCT.
10
CODE
ERR"
"PARAMET
11
ER
ERROR"
12
"MISSING
END INS."
Table 6.1 Error Code List (Continue)
Detailed
Error
CPU
Code
States
(D9092)
103
Stop
Device specified by a
dedicated instruction for CC-
Link is not correct.
104
A dedicated instruction for
CC-Link has incorrect
program structure.
105
A dedicated instruction for
CC-Link has incorrect
command name.
Stop
The contents of parameters
of CPU memory have
changed due to noise or the
improper loading of memory.
Stop
There is no
instruction in the program.
Error and Cause
(
)
END
FEND
64
Corrective Action
Read the error step using a
peripheral device and correct
the program of the step.
(1)Load the memory cassette
correctly.
(2)Read the parameter
contents of CPU memory,
check and correct the
contents, and write them
to CPU again.
Write
instruction at the
END
end of program.