Mitsubishi Electric MELSEC-A series User Manual page 84

Hide thumbs Also See for MELSEC-A series:
Table of Contents

Advertisement

Error
Error
Code
Message
(D9008)
"SP. UNIT
46
ERROR"
"LINK
47
PARA.
ERROR"
Table 6.1 Error Code List (Continue)
Detailed
Error
CPU
Code
States
(D9092)
Stop or
(1)Access (execution of
Continue
(set by
para-
meter)
462
(1)There is inconsistency in
(2)The location designated
Continue (1)There is inconsistency for
(2)The total number of sta-
Error and Cause
or
instruction)
FROM
TO
has been made to a loca-
tion where no special
function module is
installed.
the module name
between the special
instruction for CC-Link
and I/O assignment of the
parameter.
by the special instruction
for CC-Link is not the
master module.
some reason between the
data, which is written by
the peripheral device in
the parameter area of the
link under link range des-
ignation using parameter
setup, and the link param-
eter data read by the CPU
module.
tions is set at "0."
70
Corrective Action
(1)Use the peripheral device
to read and correct the
and/or
instruc-
FROM
TO
tion at the error step.
(1)Correct the module name
of I/O assignment of the
parameter to that of the
special instruction for CC-
Link.
(2)Use the peripheral device
to check and correct the
special instruction for CC-
Link at the error step.
(1)Write parameters and
check again.
(2)If the error persists, there
is a fault in hardware. Con-
sult Mitsubishi representa-
tive.