Error
Error
Code
Message
(D9008)
"CONTROL-
40
BUS ERR."
"SP. UNIT
41
DOWN"
"I/O INT.
43
ERROR"
"SP. UNIT
44
LAY.
ERROR."
Table 6.1 Error Code List (Continue)
Detailed
Error
CPU
Code
States
(D9092)
Stop
The
tions cannot be executed.
(1)Error of control bus with
Stop
There is no reply from the
special function module dur-
ing execution of the
TO
(1)The special function mod-
Stop
Interrupt occurs though no
interrupt module is installed.
Stop
(1)Three or more computer
(2)Two or more MELSEC-
(3)Two or more interrupt
(4)A special function module
(5)The I/O module or spe-
Error and Cause
and
instruc-
FROM
TO
special function module.
FROM
instruction.
ule being accessed is
faulty.
link modules are installed
for a single CPU module.
NET (II), MELSECNET /B
or MELSECNET /10 data
link modules are installed.
modules are installed.
is installed to a slot
assigned to the I/O mod-
ule with parameter setup
of the peripheral device,
or vice versa.
cial function module is
installed outside the fol-
lowing I/O number
ranges, or GOT is con-
nected to the bus.
A1SH, A1SJHCPU: X0 to
XFF
A2SHCPU(S1): X0 to
X1FF
69
Corrective Action
The hardware of the special
function module, CPU mod-
ule or base unit is faulty.
Replace the faulty module
and check the faulty module.
Consult Mitsubishi represen-
tative.
The hardware of the special
function module being
or
accessed is faulty. Consult
Mitsubishi representative.
The hardware of a module is
faulty. Replace the module
and check the faulty module.
Consult Mitsubishi represen-
tative.
(1)Reduce the number of
computer link modules to
within two.
(2)Reduce the number of
MELSECNET (II),
MELSECNET /B and
MELSECNET /10 data link
modules to one.
(3)Reduce the number of
interrupt modules to one.
(4)Using the peripheral
device, correct the param-
eter I/O assignment
according to the actual
state of installation of the
special function modules.
(5)Examine the I/O number
and remove the modules
and GOT installed outside
the range specified on the
left.