(5) Positioning Modules
Precautions to be followed when the machinery conforming to the EMC
Directive is configured using the A1SD75P -S3 are described below.
(a) When wiring with a 2 m (6.56 ft.) or less cable
• Ground the shield section of the external wiring cable with the cable
clamp.
(Ground the shield at the closest location to the A1SD75 external
wiring connector.)
• Wire the external wiring cable to the drive unit and external device with
the shortest practicable length of cable.
• Install the drive unit in the same panel.
(b) When wiring with cable that exceeds 2 m (6.56 ft.), but is 10 m (32.81 ft.)
or less
• Ground the shield section of the external wiring cable with the cable
clamp.
(Ground the shield at the closest location to the A1SD75 external
wiring connector.)
• Install a ferrite core.
• Wire the external wiring cable to the drive unit and external device with
the shortest practicable length of cable.
External wiring connector
Cable clamp
External wiring cable (within 2 m (6.56 ft.))
Drive unit
External wiring connector
Ferrite core
Cable clamp
External wiring cable (2 m to 10 m (6.56 ft. to 32.81 ft.))
9
Drive unit