Appendix B
Troubleshooting
Problem
An error occurs when configuring the module from the FP-1600 Properties
dialog box.
Possible causes
Make sure you are entering valid values for all network parameters. If the
and solutions
subnet mask or IP address is not compatible with the network settings, an error
is returned and the FP-1600 will not be configured.
Problem
The FP-1600 returns invalid time-stamp values.
Possible causes
and solutions
FieldPoint FP-1600 User Manual
Make sure that the IP address for the computer running National
Instruments Time Service is correctly configured for the FP-1600.
Make sure that National Instruments Time Service was installed on the
desired machine and is running. If Time Service is installed but is not
running, restart it.
Under Windows 98/95—Open an MS-DOS prompt and enter
c:\windows\system\timeservice -start
Under Windows NT—Open a Command Prompt and enter
c:\winnt\system32\timeservice -start
If Time Service is not installed, refer to Chapter 2,
Installation, for instructions on installing the FieldPoint software, which
includes Time Services.
B-4
Hardware and Software
www.natinst.com