INSTALLATION
9
The device must always be handled and moved in an upright
position.
9
Use a lifting bar in order to prevent the pressure exerted by the
straps from damaging the unit.
9
Do not tilt the device by more than 15°.
9
The device is heavier on the compressor side (where the electri-
cal connections are present).
1
3
1
Polyethylene film
2
Cardboard covers
3
Polystyrene panel
The handling and unpacking operations are described below:
— transport the device to the installation zone using tools that
are suitable for its weight
— remove the polyethylene film
— remove the document envelope
— removed the cardboard covers
— remove the polystyrene protection element on the cover of
the unit
0
It is forbidden to disperse the packaging materials into the en-
vironment or to leave them within the reach of children, as they
could pose a potential hazard. These must be disposed of in
accordance with the current legislation.
2
The device is secured to the pallet by 4 screws (two at the front, and
two at the back), which must be removed.
2.5

Place of installation

The location of the R NexPolar devices must be determined by
the system's designer or by another competent person, and must
take into account the technical requirements, as well as any current
local regulations that require specific permits to be obtained (e.g.:
zoning, architectural, environmental protection, etc.).
It is therefore recommended to obtain all the necessary permits be-
fore installing the device.
The R NexPolar unit is designed for outdoor installation.
It is recommended to avoid
— Positioning the unit in air shafts and/or basement window
wells.
— Any obstacles or barriers that will cause the expelled air to
recirculate.
— Locations in which aggressive atmospheres are present.
— Confined locations in which the device's sound levels might
be compounded by reverberations or resonances.
— Positioning in corners where dust, leaves, or any other mate-
rials typically accumulate, which could compromise the de-
vice's efficiency by obstructing the airflow.
— Situations in which the air expelled from the device might en-
ter the habitation through doors or windows, thus creating an
inconvenience for the people inside.
— Situations in which the air expelled from the device will en-
counter resistance from opposing winds.
— Direct exposure to sunlight and proximity to heat sources
9
If the device is to be positioned in a windy location, the fan
must be protected by a wind-proof screen, and the unit's
proper operation must be verified.
2.6

Recommended compliant zones

The compliant zones for the device's installation and maintenance
are shown in the figure. The indicated spaces are necessary in order
to prevent the airflow from being blocked, as well as to allow nor-
mal cleaning and maintenance operations to be carried out.