Positioning

The R NexPolar devices must:
— be positioned on a level surface that's capable of supporting
their weight
— be positioned on a sufficiently rigid surface that will not
transmit any vibrations to the underlying or adjacent rooms
It is recommended to place a rubber slab (hardness 60 shore, thick-
ness 10 mm.) or properly sized anti-vibration supports between the
device and its support surface.
The unit should be raised off the ground, as follows:
— 100 mm for installations in ordinary zones.
— 300 mm for installations in zones that are extremely cold or
subject to heavy snowfall
9
Adequate antifreeze systems should be used for installations
in zones that are extremely cold or subject to heavy snowfall,
where the possibility of freezing is present.
9
While operating in heating mode, the unit generates conden-
sation, which will be deposited on the support surface. This
could freeze if the outdoor temperatures are below zero, thus
creating a hazard. In this case, appropriate barriers should be
installed in order to prevent people from approaching the unit.
1
A
a
Positioning in ordinary areas
B
Positioning in very cold areas or with heavy snowfalls
1
Rubber slab
282
2.8 Installation on old systems or systems in
need of upgrading
When the R NexPolar unit is installed on old systems or systems
in need of upgrading, it is recommended to ensure that:
— the electrical system is compliant with the applicable regula-
tions and has been installed by qualified professionals
— the expansion tank ensures the complete absorption of the
expansion fluid contained within the system