Capacity Control In Night Mode - Riello NexPolar Series Installation And Technical Service Instructions

Table of Contents

Advertisement

4.11 Capacity control in night mode

The night period is defined by a start time and a stop time can be set by the user. Night mode allows the user to configure the
unit in such a way that it operates with specific parameters within a certain period of time, for example night period. In particu-
lar, this mode allows the compressor's frequency to be decreased during a certain time frame.
Steps
Table
CMP_CONF
Night mode
settings
GEN_CONF
Par.
Designation
The compressor's
frequency is limited
Power
by this percentage
541
limitation
of the maximum
value
permitted
frequency
Night mode
Night mode
518
start time
activation time
Night mode
Night mode stop
519
end time
time
Description
range
50 - 100
00:00 -
23:59
00:00 -
23:59
53
FUNCTIONS
Default
Ex.
Units
75
50
0:00
23:00
hh: mm
0:00
7:00
hh: mm
%