06 (0X06) Write Single Register" Function - Toshiba TOSVERT VF-S15 Function Manual

Hide thumbs Also See for TOSVERT VF-S15:
Table of Contents

Advertisement

8.5. "06 (0x06) Write Single Register" function

This Modbus request is used to write the value to the inverter parameter.
Request format:
Byte
0
Function Code = 06h
1
Communication No. of Parameter Hi
2
Communication No. of Parameter Lo
3
Write Data Hi
4
Write Data Lo
Response format:
Byte
0
Function Code = 06h
1
Communication No. of Parameter Hi
2
Communication No. of Parameter Lo
3
Write Data Hi
4
Write Data Lo
Exception response format:
Byte
0
Function Code = 86h
Exception Code
01: Illegal Function
1
02: Illegal Data Address
03: Illegal Data Value
04: Slave Device Failure
When you use this Modbus request, the value is written to the EEPROM.
Meaning
Meaning
Meaning
Notes
- 62 -
E6582051

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tosvert vf-as3Tosvert vf-mb1

Table of Contents