C U S T O M A P P L I C AT I O N E D I T O R M A N U A L
—
Info and error messages
—
Application Run-Time Error Codes
In the event of a Custom Application Error which is shown on the UMC panel a detailed error code can be found in the FIM
diagnostic mode on tab card diagnostics 2 (the two values on the bottom of the window). The following table explains
theses values:
Custom Application
Explanation / Corrective Measure
Status
Byte 0, Bit Number
0
Unknown function block. This might happen if a UMC received a function block application which was created for an
incompatible device version. Ensure that the firmware and function block library fit together. Re-check your application
and ensure that only supported function blocks are used.
1
Application code too large. Ensure that the firmware and function block library fit together.
2
Memory full. Decrease the number of function blocks that require instance data (e.g. counters, timers)
3-6
Reserved
7
Internal error
Custom Application
Status
Byte 1, Bit Number
1
Checksum error. Please reload the application into the UMC.
2
Wrong UMC version. The application was compiled for a different UMC version. Ensure that the firmware and function
block library fit together.
3
Wrong runtime system version. The application was compiled for a different UMC version. Ensure that the firmware and
function block library fit together.
4
Wrong device description file version. The application was compiled for a different UMC version. Ensure that the firmware
and function block library fit together.
5
Timeout during application timeout. Reload the application.
6
Application too large. As the Custom Application Editor checks the max. possible size the application was compiled for a
different UMC version. Ensure that the firmware and DTM version fit together.
7
Motor control function block not as paramtriesed in the parameters. The configured motor control function must fit to
the used control function block.