Function block reference
Actuator 1- 4
Use this function in a feeder that requires an open/close valve to be controlled. Select the actuator block that fits your
requirements regarding limit and torque inputs.
Function Block
Inputs (from top to bottom)
Outputs (from top to bottom)
Parameters
Signal Name
Rev (Close): Start motor in a reverse direction..
Stop: If logical 1 the motor will be stopped and cannot be started until the input changes to
logical 0 level.
For (Open): Start motor in a forward direction.
Limit Switches Opening / Closing: Inputs to signal the status of the limit switches.
Torque Open Closed: Input signalling the status of the torque switches.
DO2... DO3: Inputs not used from the starter. Depending on the fault output configuration
also DO2/DO3 is controlled by the function block.
Rev Status (Close): If the motor is running in a reverse direction the output is set to logical 1.
Stop Status: If the motor has been stopped this output is set to logical 1.
For Status (Open): If the motor is running in a forward direction the output is set to logical 1.
Open: If the valve is open (i.e. end positions left) this output is set to logical 1.
Close: If the valve is closed (i.e. in end position) this output is set to logical 0
Rev Lockout Time Running: When logical 1 the lockout time is running and a start signal is
ignored.
Out of Position: There is a positioning error.
Run Time Exceeded: Time between opening and closing is longer than permitted by the user
configuration.
Status DO0 ... DO3: Mirror of the digital outputs of the UMC.
See section "Control Function Actuator 1-4" in the UMC100 manual.
Data Type
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean