C U S T O M A P P L I C AT I O N E D I T O R M A N U A L
Function block reference
Reversing Starter (REV)
Use this function in a feeder that requires a motor to start/stop in two directions of rotation (forward / backwards).
Function Block
Inputs (from top to bottom)
Output (from top to bottom)
Parameters
Signal Name
Rev: Start motor in a reverse direction
Stop: If logical 1 the motor will be stopped and cannot be started until the input changes to
logical 0 level.
For: Start motor in a forward direction
Voltage DIP: Signals a voltage DIP situation which is triggered by an external device (e.g.
central voltage monitor).
DO2 / DO3: Inputs not used from the starter. Depending on the fault output configuration
also DO2/DO3 is controlled from the function block.
Rev Status (Reverse): If the motor is running in reverse direction the output is set to active 1
Stop Status: If the motor has been stopped this output is set to active 1
For Status (Forward): If the motor is running in forward direction the output is set to active 1
CB Fault: A checkback fault has occurred.
Start Time Run: During motor start this output is set to logical 1.
Status DIP: Signals that the voltage DIP function is active. See UMC100 manual for more
information about voltage DIP.
Rev Lockout Time Running: When locical-1 the lockout time is running and a start signal is
ignored.
Status DO0 ... DI3: Mirror of the digital outputs of the UMC.
See section "Control Function Reversing Starter" in the UMC100 manual.
57
Data Type
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean