32
C U S T O M A P P L I C AT I O N E D I T O R M A N U A L
Function block reference
Binary Monitoring Acyclic
The function bocks "Binary Monitoring Acyclic 0 ... 1" provide access to the monitoring bytes 0 ... 1 acyclically sent via fieldbus
(e.g. PROFIBUS). Monitoring data is sent from the UMC to the fieldbus master (e.g. a PLC) only upon request.
The monitoring bytes can be read at slot 4 / index 7 (Binary Monitoring Acyclic 0) and index 8 (Binary Monitoring Acyclic 1). 8
Bytes must be read whereas byte 0 represents the monitored byte.
Function Block
Inputs (from top to bottom)
Outputs
Parameters
Analogue Monitoring
The function blocks "Analog Monitoring" provide access to the monitoring words 0 ... 4 which are sent cyclically via fieldbus
(e.g. PROFIBUS) to the master. Monitoring data is sent from the UMC to the Fieldbus master (e.g. a PLC) on request only.
Function Block
Inputs (from top to bottom)
Outputs
Parameters
Signal Name
In 0 ... In7: The 8 bits of the monitoring byte 0, 1, 2, 3, 4 or 5
-
-
Signal Name
In 0 (W) ... In 4 (W): The five monitoring words.
-
-
Data Type
-
-
Data Type
Word
-