ABB UMC100.3 Manual page 62

Custom application editor, universal motor controller
Hide thumbs Also See for UMC100.3:
Table of Contents

Advertisement

62
C U S T O M A P P L I C AT I O N E D I T O R M A N U A L
Function block reference
Softstarter
Use this function to control a softstater in one or two directions of rotation. Usually this control function is used together
with softstarters without own communication interface.
Function Block
Inputs (from top to bottom)
Outtput (from top to bottom)
Parameters
Signal Name
Rev: Run reverse signal, rising edge
Stop: Stop signal
For: Run forward signal, rising edge
DO3: Input to freely control DO3 if not used as fault output
Delay1: Delay for softstarter start output signal DO2
0...100 [0.1s], if input is >100 the value is set to 100
Delay2: Off-Delay for DO0 and DO1 after ramp down
0...100 [0.1s], if input is >100 the value is set to 100
Rev/Stop/For Status: Motor status
CB Fault: Checkback fault detected
Rev Lockout Time Running: Reversing lockout time is running
Ramp Up/Down Time Running: Ramping up, ramping down
Status DO0 ... DO3: Status of the outputs
See section "Control Function Softstarter" in the UMC100 manual.
Data Type
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean