C U S T O M A P P L I C AT I O N E D I T O R M A N U A L
Function block reference
Inputs (from top to bottom)
Outputs (from top to botton)
Parameters
The outputs FRev, Rev, For and FFor are set if there is a start signal at the related inputs. If the connected
starter function block cannot start for any reason (e.g. cooling time still running, lockout time running) the
above mentioned outputs are reset automatically. A new start signal must be issued to trigger another start.
Signal Name
Force Local 2, Auto:
These two inputs allow you to select one out of the three modes "Local 1", "Local 2" and "Auto".
The table below shows the selected mode based on the three input signals.
Busfault
1
(internal signal)
Force Local 2
x
Auto
x
Resulting Mode
Local 1
FRevCyclic (Fast Reverse Cyclic), RevCyclic (Reverse Cyclic), StopCyclic, ForCyclic (Forward
Cyclic), FForCyclic (Fast Forward Cyclic):
These command inputs are intended to be connected to a cyclic fieldbus telegram (command
telegram) function block - e.g. the Command byte 0 and Command byte 1 blocks.
FRev DIO (Fast Reverse), Rev DIO (Reverse Cyclic), Stop DIO, For DIO (Forward), FFor DIO (Fast
Forward):
These command inputs are intended to be connected to the digital inputs of the UMC e.g. the
"Basic DI" function block.
FRev LCD (Fast Reverse), Rev LCD (Reverse Cyclic), Stop LCD, For LCD (Forward), FFor LCD (Fast
Forward):
These command inputs are intended to be connected to the LCD panel function block.
FRev Acyclic (Fast Reverse), Rev Acyclic (Reverse Cyclic), Stop Acyclic, For Acyclic (Forward),
FFor Acyclic (Fast Forward):
These command inputs are intended to be connected to one of the acyclic command function
blocks.
FRev (Fast Reverse), Rev (Reverse), Stop, For (Forward), FFor (Fast Forward):
These outputs are command outputs and usually connected to a starter block (e.g. DOL).
Auto Status: Indication that the auto mode is active for command selection.
Local 1 Status: Indication that the Local 1 mode is active for command selection.
Local 2 Status: Indication that the Local 2 mode is active for command selection.
See sections "Configuring the Motor Management Functions" and " Configuring the Fieldbus Communication->
Defining the Bus Fault Reaction" in the UMC100 manual.
0
0
0
1
0
x
Local 1
Local 2
Data Type
Boolean
0
0
1
Auto
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean