C U S T O M A P P L I C AT I O N E D I T O R M A N U A L
Info and error messages
During editing and on user request the custom application is checked against a number of design
rules to ensure a valid application. Design rules can either lead to an error message or a warning.
Messages are displayed in the message window.
Messages are not stored and are deleted if the configuration application is closed.
Each warning and error is uniquely identified with a number.
The following table lists all messages with possible corrective measures.
Error / Warning Code
Explanation / Corrective Measure
1000
Connection of a boolean port to a word port. Only connections between ports of the same data types are allowed.
1001
The size of an application is limited. The limit was reached.
1002
A function block has a port which is no longer available in the presently selected function block library. Select the function
block library version that was used when the diagram was created. Or delete the function block and replace it with the
version available in the presently selected library.
1003
The source block of a connection is missing.
1004
The sink block of a connection is missing.
1005
The port cannot be negated.
1006
An application requires exactly one function block from group "Control Functions".
1007
A function block was not added to the program because either all the inputs or outputs are disconnected. i.e. the function
block is meaningless.
1008
A constant value is not supported at this position.
1009
The application running in the UMC is different from the one in the application editor (checksum differs).
1010
Time constants are internally handled with a resolution of 100ms. The provided value was inbetween two 100ms steps
and was rounded to the next 100ms step.
1011
The given delay time was larger than the max. supported value.
2001
The number of instances per function block type is limited. The limit for a certain type of function block was reached.
2002
The size of an application is limited. The limit was reached.
2003
An application requires exactly one function block from group „Control Functions".
2004
A design rule was violated (e.g. number of function blocks).
2005
The instance name of each function block must be unique. By default unique names are choosen. If they are modified by
hand unique names must be used.
2006
The selected starter function block is different from the selected control function. Both must match.
3001
Internal error. Please report it to your responsible sales contact. Use the template provided at the end of the document.
3002
There is an inconsistency between the application and the selected function block version. Ensure that the library version
is selected that was used when the application was created.
3003
No function block library version was selected. Select the version supported by the used UMC.
3004
A previously exported application could not be imported anymore. Most probably the file is corrupt.
3005
A previously exported application could not be imported anymore. Most
probably the file is corrupt.
3006
There is an inconsistency between the application and the selected function block version. Ensure that the library version
is selected that was used when the application was created.
9999
Internal error. Please report it to your responsible sales contact. Use the template provided at the end of the document