C U S T O M A P P L I C AT I O N E D I T O R M A N U A L
Function block reference
VI15x Voltage
This function block provides access to all the process values and status signals from the voltage measurement module.
Function Block
Outputs
Inputs
Parameters
Signal Name
Average Voltage [V]: Average voltage of U
UL1L2, UL2L3, UL3L1: Line voltages
Overvoltage Trip/Warn: True if one line voltage is above the adjusted overvoltage trip/warn
level.
Undervoltage Trip/Warn: True if one line voltage is below the adjusted undervoltage trip/warn
level.
Phase Loss: One or more phases are lost (e.g. fuse blown)
U Imb.: The voltage imbalance value
U Imb. Trip/Warn: True if the voltage imbalance is above the adjusted trip/warn level.
Wrong Phase Sequence: Output is set if a wrong phase sequence was detected.
THD L1, L2, L3: Total harmonic distortion on the phase.
THD Warn: Output is set if the total harmonic distortion is above the configured warn level in a
phase.
-
U Imb. Trip Level, U Imb. Trip Delay, U Imb. Warn Level, U Imb. Warn Delay,
THD Warning Level, THD Warning Delay
U Low Trip Level, U Low Trip Delay, U Low Warn Level, U Low Warn Delay, U High Trip Level, U High Trip Delay, U
High Warn Level, U High Warn Delay
, U
, U
L1L2
L2L3
L3L1
Data Type
Word
Word
Boolean
Boolean
Boolean
Word
Boolean
Boolean
Word
Boolean
-