Function block reference
—
VI15x Voltage
This function block provides access to all the process values and status signals from the voltage measurement module.
Function Block
Outputs
Inputs
Parameters
Signal Name
Average Voltage [V]: Average voltage of U
UL1L2, UL2L3, UL3L1: Line voltages
Overvoltage Trip/Warn: True if one line voltage is above the adjusted overvoltage trip/warn
level.
Undervoltage Trip/Warn: True if one line voltage is below the adjusted undervoltage trip/warn
level.
Phase Loss: One or more phases are lost (e.g. fuse blown)
U Imb.: The voltage imbalance value
U Imb. Trip/Warn: True if the voltage imbalance is above the adjusted trip/warn level.
Wrong Phase Sequence: Output is set if a wrong phase sequence was detected.
THD L1, L2, L3: Total harmonic distortion on the phase.
THD Warn: Output is set if the total harmonic distortion is above the configured warn level in a
phase.
-
U Imb. Trip Level, U Imb. Trip Delay, U Imb. Warn Level, U Imb. Warn Delay,
THD Warning Level, THD Warning Delay
U Low Trip Level, U Low Trip Delay, U Low Warn Level, U Low Warn Delay, U High Trip Level, U High Trip Delay, U
High Warn Level, U High Warn Delay
, U
, U
L1L2
L2L3
L3L1
Data Type
Word
Word
Boolean
Boolean
Boolean
Word
Boolean
Boolean
Word
Boolean
-