C U S T O M A P P L I C AT I O N E D I T O R M A N U A L
Function block reference
Star-Delta Starter
Use this function in a feeder that requires the motor to start in star-delta mode.
Function Block
Inputs (from top to bottom)
Output (from top to bottom)
Parameters
Signal Name
Stop: If logical 1 the motor will be stopped and cannot be started until the input changes
to logical 0 level.
For: Start motor
DO3: Output not used from the starter. Depending on the fault output configuration also
DO3 is controlled by the function block.
Stop Status: If the motor has been stopped this output is set to active 1
For Status (Forward): If the motor is running the output is set to active 1
CB Fault: A checkback fault has occurred.
YD Starting Time: This output is logical 1 in star mode and logical 0 in delta mode.
Start Time Run: During motor start this output is set to logical 1.
Status DO0 ... DI3: Mirror of the digital outputs of the UMC.
See section "Control Function Star-Delta Starter" in the UMC100 manual.
Data Type
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean