Self-Diagnostic Function; Led Display For Status Condition; Operation On Error - Panasonic FP E Series User Manual

Table of Contents

Advertisement

8.1 Self-Diagnostic function

8.1.1 LED Display for Status Condition

Status indicator LEDs on control unit
RUN
Light (on)
Normal
Off
condition
Flashes
Light (on)
Abnormal
Off
condition
• The control unit has a self-diagnostic function which
identifies errors and stops operation if necessary.
• When an error occurs, the status of the status indicator
LEDs on the control unit vary, as shown in the table above.

8.1.2 Operation on Error

• Normally, when an error occurs, the operation stops.
• The user may select wheter operation is to be continued or stopped when a duplicated output error or
operation error occurs, by setting the system registers. You can set the error which operation is to be
continued or stopped using the programming toolshoftware as shown below.
"PLC System Register" setting menue on programming tool software
To specify the steps to be taken by the FPWIN GR if a PLC error occurs, select "PLC System Register
setting" under "Option" on the menu bar, and click on the "Action on Error" tab.
The screen shown below is displayed.
8-2
LED status
ERROR/
PROG.
ALARM
Off
Off
Light (on)
Off
Flashes
Off
Off
Flashes
Light (on)
Flashes
Light (on)
Description
Normal operation
PROG. mode
Forcing on/off in Run mode
When a self-diagnostic error
occurs
Shen a self-diagnostic error
occurs
System watchdog timer has
been activated
Example1]: When allowing duplicated
output
Turn off the check box for No. 20. When
operation is resumed, it will not be handled
as an error.
[Example2]: When continuing operation
even a calculation error has occurred
Turn off the check box for No. 26. When
operation is resumed, it will be continued, but
will be handled as an error.
Operation
statuss
Operation
Stop
Operation
Operation
Stop
Stop