Procedure of Program Conversion
1. Retrieve a program to be converted with FPWIN GR.
6. For the program using the hold-type area in the internal relay (R900 to R97F and WR90 to WR97), the
device should be changed to the hold-type area for the FPΣ 32k type (R2480 to R255F and WR248 to
WR255).
2. Select "Option" → "PLC
Configuration" in the menubar.
Note down the setting value for the
system registers.
3. Select "Tool" → "Change PLC Type".
Select "FPSIGMA 32K" and click "OK" button.
4. A message "System register formatted." is indicated.
Click "OK" button.
5. Select "Option" → "PLC Configuration".
Input the values noted down in procedure
2.
Note) When the battery is not used, the
system register No. 7 "Hold type area
starting word address for internal relay"
should be set to "248" that is the default
value for the FPΣ 32k type.
Select "Edit" → "Change Device".
Click the
buttons of "Source" and "Destination" to
select "R" and "WR" from the pulldown menu, and
change the values.