*2: specification of duty (specify using K constant)
If the control code is K0 to K19, the duty is K0 to K999 (0.0% to 99.9%).
If the control code is K20 to K24, the duty is K0 to K990 (0% to 99%).
Values are specified in units of 1% (K10) (digits behind the decimal point are rounded off).
Note:
• If a value outside the specified range is written to the duty area while the instruction is being executed,
a frequency corrected to the maximum value is output. If written when instruction execution is started,
an operation error is occurred.