Name
Boolean
Leading
AN↑
edge AND
Trailing edge
AN↓
AND
Leading
OR↑
edge OR
Trailing edge
OR↓
OR
Leading
OT↑
edge out
Trailing edge
OT↓
out
Alternative
ALT
out
AND stack
ANS
OR stack
ORS
Push stack
PSHS
Read stack
RDS
Pop stack
POPS
Leading
DF
edge
differential
Trailing edge
DF/
differential
Symbol
Connects a Form A (normally open) contact serially only
for one scan when the leading edge of the trigger is
detected.
Connects a Form A (normally open) contact serially only
for one scan when the trailing edge of the trigger is
detected.
Connects a Form A (normally open) contact in parallel only
for one scan when the leading edge of the trigger is
detected.
Connects a Form A (normally open) contact in parallel only
for one scan when the trailing edge of the trigger is
detected.
Outputs the operated result to the specified output only for
one scan when leading edge of the trigger is detected. (for
pulse relay)
Outputs the operated result to the specified output only for
one scan when trailing edge of the trigger is detected. (for
pulse relay)
Inverts the output condition (on/off) each time the leading
edge of the trigger is detected.
Connects the multiple instruction blocks serially.
Connects the multiple instruction blocks in parallel.
Stores the operated result up to this instruction.
Reads the operated result stored by the PSHS instruction.
Reads and clears the operated result stored by the PSHS
instruction
Turns on the contact for only one scan when the leading
edge of the trigger is detected.
Turns on the contact for only one scan when the trailing
edge of the trigger is detected.
Description
Steps
(*1)
2
2
2
2
2
2
3
1
1
1
1
1
1
1
12-37